FSP UPS CHAMP 1KVA LONG RUN W/O BATTERY

 15,840.00

Key Features
1True double conversion
2Microprocessor control optimizes reliability
3Input power factor correction
4Output power factor 0.9
5Wide input voltage (120V-300V)
6Converter mode available
7ECO mode for energy saving
8Generator compatible
9Smart SNMP works well with either USB or RS-232 together
10Comprehensive display allows easy monitoring and access of UPS status

Category:

MODELChamp 1K
PHASESingle phase with ground
CAPACITY1000 VA / 900 W
INPUT
Nominal Voltage200/208/220/230/240 Vac
Voltage Range110-300 Vac (Based on load at 50%)

160-280 Vac (Based on load at 100%)

Frequency Range40Hz ~ 70 Hz
Power Factor≧ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage200/208/220/230/240 Vac
Voltage Regulation± 1%
Frequency Range (Synchronized Range)47~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode)50Hz ± 0.25Hz or 60Hz ± 0.3Hz
Inverter Crest Ratio3:1
Harmonic Distortion (THDv)≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
Transfer Time
AC Mode to Battery ModeZero
Inverter to Bypass4 ms (Typical)
Waveform (Batt. Mode)Pure Sinewave
EFFICIENCY
AC Mode

88%
Battery Mode83%
BATTERY
Standard Model
Battery Type12 V / 9 Ah
Numbers in string2
Typical Recharge Time4 hours recover to 90% capacity
Charging Current (max.)1.0 A
Charging Voltage27.4 Vdc ± 1%
Long-run Model
Battery TypeDepending on the capacity of external batteries
Numbers in string2
Charging Current (max.)1A/2A/4A/6A (Adjustable)
Charging Voltage27.4 Vdc± 1%
INDICATORS
LCD PanelLoad level, Battery level, Line mode, Battery mode, Bypass mode, ECO mode and Fault indicators
ALARM
Battery ModeBeeps every 4 seconds
Low BatteryBeeps every second
OverloadBeeps twice per second
FaultContinously beeping
PHYSICAL
Standard Model
Dimension, D x W x H (mm)282 x 145 x 220
Net Weight (kgs)9.8
Long-run Model
Dimension, D x W x H (mm)282 x 145 x 220
Net Weight (kgs)4.1
ENVIRONMENT
Humidity20-90 % RH @ 0- 40°C (non-condensing)
Noise LevelLess than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, and MAC
Optional SNMPPower management from SNMP manager and web browser

 
* Product specifications are subject to change without further notice



Exclusive Products